• head_banner

Rail-mounted DC Power Meter, DJSF1352-RN

Rail-mounted DC Power Meter, DJSF1352-RN

● Measurement: kWh, kVarh, Power, Current, Voltage and etc

● Current Rating: Shunt 0-75mV; Hall sensor 0-20mA,4-20mA,0-5 V,0-10V

 Voltage Rating: 0~1000V DC

● Application: DC Battery; Charging Pile; Solar PV and etc

● Communication: DL/T645-2007 Protocol, MODBUS-RTU Protocol

 Power Supply: 85~265V AC/DC; 24V(±10%) DC; 48V(±10%) DC

 Pulse Input: One Second pulse output, one electric energy pulse output

● Display: 8 Digital Segment type LCD

● Dimension: 72*71*87.8mm (L*W*H)

● Installation: 35mm DIN Rail

● Standard&Certificate: CE


Product Detail

Technical parameters

Download

Overview

Designed with double DC input channels, DJSF1352-RN rail-mounted DC power meter is particularly built for measurement of voltage, current, power, positive and negative electric energy in DC systems, which can be widely used in base stations, DC charging stations, photovoltaic systems, etc. This power meter is capable of measurement of total value, as well as measurement of values in different time periods.

1

 SOE Event Record

 Infrared Communication

 BI-Direction Active Power Measuring

 Multi-Tariff Function

 8 Digital LCD Display

 Maximum Voltage Output 1000V 

LCD Display

微信截图_20230302101343

Product Size

2
3

Features

4

Wiring

1
3926839ee13b7079737de11166457f5

Installation

7

Application

微信截图_20230310161000
微信截图_20230310161117
微信截图_20230310161145

Technical parameters

Index

Input

Nominal value

Voltage input range

Current input

 

 

DC 0-1000V
See the physical wiring diagram

Shunt:0-75mV;
Hall sensor:0-20mA、4-20mA、0-5V,0-10V and so on.

 

 

 

 

 

Overload

1.2 times rated (continuous); 2 times rated/1 second;

 

Power consumption

Voltage: ≤0.2VA, current ≤0.1VA

Accuracy class

Class 1 or Class 0.5

Function

Display

8-bit segment LCD screen (LCD)

 

Communication Interface

RS485(two options)

 

Communication protocol

Modbus-RTU,DL/T 645-2007

 

Switch

Switch output

2 Relay outputs, 2A/30VDC or 2A/250VAC

 

 

Switch input

2 dry contact inputs

 

Pulse output

A second pulse output, a energy pulse output

 

 

See the SYS->PLUS display in the meter menu settings. For example: The meter displays 100, which is 100imp/kWH

Power Supply

Voltage range

AC/DC 85-265V or DC24V(±10%) or DC48V(±10%)

 

Power consumption

≤ 3W

Power frequency withstand voltage

Power supply // Voltage input // Current input // Relay output and switch input // Communication interface / / Pulse output 3kV/1min
Power supply // Relay output // Voltage input // Current input 3kV/1min
Pulse output // Communication interface // Switch input 2kV/1min

Impulse withstand voltage

±6KV

Insulation resistance

≥ 40M Ω

Average barrier-free working hours

≥50000h

Environment

Temperature

Normal operating temperature: -25 °C ~ +65 °C; Limit working temperature: -40 °C ~ +70 °C;
Storage temperature: -40℃~+80℃

 

Humidity

≤93%RH, no condensation, no corrosive gas

 

Altitude

≤2500m

Pulse constant

Maximum power

 

999.9W

10000

imp/kWh

9.999kW

1000

imp/kWh

99.99kW

100

imp/kWh

999.9kW

10

imp/kWh

9999kW

1

imp/kWh

Maximum power = rated voltage * voltage ratio * current ratio * 1.2
Write your message here and send it to us