Multi-loop Power Meter for IDC (Internet Data Center), AMC16Z-FAK48
Multi-loop Power Meter for IDC (Internet Data Center), AMC16Z-FAK48
AMC16Z series multi channel din rail ac power meter is independently designed to meet the needs of the increasingly high precision power distribution management requirements of the data center. It is suitable for carious all-round inrelligent monitoring of terminal distribution equipment.
* 24 channels of each circuit of A+B
*independent 2 circuits the outgoing current,
*active power, active power, reactive power
* 2-31st harmonic, 48DI
* 1 RS485 communication
*Installation:
DIN rail 35mm
* Dimension(L*W*H):
180*94.3*75mm
Technical Parameter | Value | |
Distribution System | AC | |
Measurement of electrical parameters |
I,U,P,Q,EP,EQ,S; | |
2-3rd harmonic | ||
24 channels on each side (48 in total) | ||
48DI | ||
RS485 | ||
Current |
CT | XXA/50mA |
Range | 0~120% | |
Overload | 1.2 times for continuous, and 10 times/second for instantaneous | |
Frequency | 45~65Hz | |
Accuracy | Class 0.2(U/I) Class 0.5(P/EP)Class 1(Q/EQ) | |
Auxiliary Supply | DC12V | |
Insulation resistance | 100MQ | |
Environmen | Temperature | Operation:-15℃~55℃ Storage:-25℃~70℃ |
Humidity | Relative humidity≤93% | |
Altitude | ≤2500m | |
Communication | RS485(Modbus-RTU) | |
Installation | DIN 35mm | |
Switch input | 48 DI |