Microcomputer Protection Device,AM3SE

Microcomputer Protection Device,AM3SE

● A complete set of protection, related to the application;

● 5 current input, 3 voltage input, 11 DI, 5DO;

● Auxiliary power supply adapts with AC220V, DC220V, DC110V, AC110V;DC48V,DC24V;

● 1 RS485 serial communication, IEC60870-5-103 and Modbus-RTU;

● 1 GPS for GPS timing;

● more than 200 sequence of event records, more than 400 system logs, and more than 10

● seconds tripping context records;

● Powerful graphic programmable Logic


Product Detail

PARAMETER

Download

Overview

The AM3SE series microcomputer protection device integrates protection ,control and is suitable for user terminal substations (stations) with a voltage level of 35kV and below .Can realize the protection and control of user substations. The application fields cover electric power, water conservancy, transportation, petroleum, chemical industry, coal, metallurgy and other industries.
The protection device adopts advanced, mature , reliable protection principles and algorithms.With strong anti-interference performance, high reliability, flexible protection implementation mode, and redundant design for communication. The device can cooperate with the Acrel-2000Z power monitoring system to provide guarantee for the reliable operation of the user's substation power distribution automation system.

Operation Instruction

d784f62ddc02fbf56254998fdcececb

Characteristic 

●Rich protection functions
Feeder protection;
Transformer protection;
Voltage protection;
●Measurement
RMS current values;
RMS voltage values;
frequency;
Power factor;
RMS active power.
●Control functions
Remote control;
Local control;
Programmable switchgear interlocking;

HG9A5223(1)

Operation process

dce811e9204a2fe8ba68b7f0eb48158

LCD Display

22ebb5d8c51eb7d5df71f7d7f1407d7
1dc53a417a08c284e852bc83bdc30ca

Protection functions

AM3SE-

I

U

Overcurrent (3 stages,IDMT)

 

Earth fault (3 stages,IDMT)(I01/I02)

 

Negative sequence overcurrent (2 stages,IDMT)

 

Auto-reclose

 

Overload (trip/alarm)

 

Under frequency

 

Post-accelerated overcurrent

 

Post-accelerated overcurrent(I01/I02)

 

Overvoltage(trip)

 

Undervoltage (trip)

 

Self-produced over zero-voltage (trip)

 

Residual overvoltage (trip)

 

FC block

 

Trip and close circuit supervision (alarm)

 

Non-electricity (trip/alarm)

 

Undervoltage (alarm)

Overvoltage (alarm)

Residual overvoltage (alarm)

PT supervision (alarm)

Self-produced over zero-voltage (alarm)

 

Rear ports

I

U

RS485

Protocols

I

U

Modbus serial

IEC 60870-5-103

Measurement

I

U

Electric parameter

U,I,P,Q,PF,Fr,Ep,Eq,Es

Input Current

5

0

Input Voltage

3

3

Logs and Records

I

U

Fault recorder

Sequence of event record

Monitoring Functions

I

U

Anti-pumping circuit

Optional

 

Remote control

Power supply

Rated input

AC/DC220V, or AC/DC110V, or DC48V, or DC24V

Range

Rared Voltage×1±20%

Consumption

≤10W ( DC )

Rated Voltage

Rated input

AC 100V/100/V

Range

1120V

Accuracy

±0.5%

Consumption

≤0.5VA  (single phase)

Rated Current

Rated input

AC 5A /1A

Range

0.04In15In

Accuracy

±0.5%

Consumption

≤0.5VA  (single phase)

Frequence

Rated frequency

50Hz or 60Hz

Range

4555Hz or 60Hz

Accuracy

±0.1Hz

DI

 Rated Voltage

AC/DC220V, or AC/DC110V, or DC48V, or DC24V

Range

Rared Voltage×1±20%

Cconsumption

≤1WDC220V(single channel)

DO

 Mechanical life

≥10000

Switching capacity

≥1000WL/R = 40ms

On current

 continuous ≥5A, short time200ms≥30A

 Interrupting capacity

≥30WL/R = 40ms

Environment

Temperature

-10℃~+55℃

Humidity

5%~95(No condensation and freeze inside)

Altitude

≤4000m