• head_banner

Medical Insulation Transformer,AITR

Medical Insulation Transformer,AITR

 Insulation Transformer for Medical IT Power System

● Low noise level 40dB

● Inrush current 12In

● Double Insulation Treatment

● Electrostatic Shielding Layer

● PT100 Temperature Sensor Embedded in the Winding

● CE; IEC 61558-1:2009; IEC 61558-2-15:2011; IEC60364-7-710:2016 


Product Detail

Parameters

Download

General

AITR series isolation transformer is specially used in medical IT system. The transformer core is made of silicon steel sheet, the loss is small. Double insulation treatment is adopted between windings, and a static screen is designed to reduce the electromagnetic interference between the two windings. PT100 temperature sensor is installed in the winding, which can be used to monitor the winding temperature. The transformer is treated by vacuum impregnation, which increases the mechanical strength and has anti-corrosion effect. In addition, the product also uses low temperature rise and low noise design, so that it has good temperature rise performance and low noise

Dimension

1

External Dimensions of AITR Series Medical Isolation Transformer

Type

Capacity (VA)

A(mm)

B(mm)

C(mm)

D(mm)

E(mm)

F(mm)

Total weight (kg) (mm) (mm) (kg)

AITR10000

10000

280

240

427

240

190

11*8

92

AITR8000

8000

280

240

427

240

190

11*8

90

AITR6300

6300

280

225

427

240

175

11*8

75

AITR5000

5000

280

225

427

240

175

11*8

73

AITR3150

3150

280

215

427

240

175

11*8

53

Wiring

2

Typical Connection

3
4

Typical Solution 1

1

Typical Solution 2

2

Typical Solution 3

3

Typical Solution 4

4

Typical Application

5

Technical Parameters of AITR Series of Medical Isolation Transformer

Type

AITR10000

AITR8000

AITR6300

AITR5000

AITR3150

Insulation class

H

H

H

H

H

Protection class

IP00

IP00

IP00

IP00

IP00

Power/voltage/ current

 

 

 

 

 

Rated power

10000VA

8000VA

6300VA

5000VA

3150VA

Rated frequency

50/60Hz

50/60Hz

50/60Hz

50/60Hz

50/60Hz

Rated input voltage

AC230V

AC230V

AC230V

AC230V

AC230V

Rated input current

45.3A

36A

28.5A

22.5

14.2A

Rated output voltage

AC230V/115V

AC230V/115V

AC230V/115V

AC230V/115V

AC230V/115V

Rated output current

43.5A

34.7A

27.4A

21.7

13.7A

Inrush current

<12In

<12In

<12In

<12In

<12In

Leakage current

<200μA

<200μA

<200μA

<200μA

<200μA

No load input current

1.359A

1.08A

0.855A

0.675A

0.426A

No load output voltage

235V±3%

235V±3%

235V±3%

235V±3%

235V±3%

Short circuit voltage

<6.9V

<6.9V

<6.9V

<6.9V

<7.5V

General parameters

 

 

 

 

 

Fuse wire

80A

63A

50A

35A

25A

Primary winding resistance

<55mΩ

<64mΩ

<80mΩ

<131 mΩ

<245mΩ

Secondary winding resistance

<45mΩ

<64mΩ

<80mΩ

<116 mΩ

<228mΩ

Iron loss

<150W

<105W

<107W

<77W

<55W

Copper loss

<230W

<200W

<170W

<125W

<120W

Efficiency

>96%

>96%

>96%

>96%

>95%

Maximum ambient temperature

<40℃

<40℃

<40℃

<40℃

<40℃

No-load temperature rise

<36℃

<33℃

<31℃

<26℃

<22℃

Full load temperature rise

<65℃

<76℃

<67℃

<62℃

<55℃

Noise grade

<40dB

<40dB

<40dB

<40dB

<40dB

 

Write your message here and send it to us