Infrared Temperature Measurement Solution,AMB300-Z
Infrared Temperature Measurement Solution,AMB300-Z
AMB infrared temperature measurement solution is a non-contact infrared temperature measurement device. The product can solve the problem of safe and accurate temperature measurement of busbar slot, upload the temperature data of each phase in the connector to the background in real time, implement monitoring and warning information, and prompt the management personnel to pay attention to the alarm point or take necessary preventive measures. The device is mainly used in the on-line temperature monitoring system of densely insulated bus connector in various fields.
Name | Model |
Function description |
Infrared temperature measurement module |
AMB300-Z |
Two-bus communication, real-time online detection of a large-scale array temperature. It needs to be used with an infrared temperature measurement collector and powered by the collector. |
AMB300-Z-T | Two-bus communication, real-time online detection of a large-range array temperature, and an external NTC temperature measurement. It needs to be used with an infrared temperature measurement collector and powered by the collector. | |
AMB300-Z-H | Two-bus communication, real-time online detection of a large-scale array temperature and humidity at the connector. It needs to be used with an infrared temperature measurement collector and powered by the collector. | |
AMB300-Z-TH | Two-bus communication, real-time online detection of a large-range array temperature, humidity at the connector, and an external NTC temperature measurement. It needs to be used with an infrared temperature measurement collector and powered by the collector. | |
AMB300-D1 | Two-bus communication, real-time online detection of a single point temperature in a small range. It needs to be used with an infrared temperature measurement collector and powered by the collector. | |
AMB300-D1-T | Two-bus communication, real-time online detection of a single point temperature in a small range, and an external NTC temperature measurement. It needs to be used with an infrared temperature measurement collector and powered by the collector. |
The arrow in the figure above indicates the direction of 24-30V signal output. The communication port needs to use a SHIELDED RJ45 cable. The left RJ45 port on the AMB300 module in the figure above is the signal incoming port, and the right RJ45 port is the signal outgoing port, which is used to connect to the incoming port of the next module.
Note: 1. The network cable should be above CAT5E.
2. A collector (AMB310) has two interfaces on the downstream two buses. Each interface is installed with a maximum of 80 infrared temperature measurement modules, and the length of each two buses is less than or equal to 250 meters.
Instrument model |
AMB300-Z |
AMB300-D4 |
AMB300-D1 |
|
Measurement |
Function |
Measuring range temperature, display the highest 4 channels, humidity (optional) |
4-way temperature |
1-way temperature and humidity(optional) |
Range |
Temperature -10℃~150℃, humidity 0%RH-95%RH |
Temperature -10℃~150℃ |
Temperature -10℃~150℃,humidity 0%RH-95%RH |
|
Accuracy |
(-10℃~85℃) temperature ±3℃, (85℃~150℃) temperature ±5℃, humidity ±5%RH |
(-10℃~85℃)temperature±3℃,(85℃~150℃)temperature±5℃ |
(-10℃~85℃)temperature±3℃,(85℃~150℃)temperature±5℃,humidity±5%RH |
|
NTC temperature measurement range (optional) |
Temperature -10℃~150℃ |
Temperature -10℃~150℃ |
Temperature -10℃~150℃ |
|
Auxiliary supply |
Power supplied by AMB310 |
Power supplied by AMB310 |
Power supplied by AMB310 |
|
Communication |
Two channels |
Two channels |
Two channels |
|
Protection level |
IP51 |
IP51 |
IP51 |
|
Pollution level |
2 |
2 |
2 |
|
Electromagnetic compatibility |
Antistatic interference |
Level 4 |
Level 4 |
Level 4 |
Anti-electric fast transient burst |
Level 4 |
Level 4 |
Level 4 |
|
Environment |
Whole machine temperature |
Working:-20℃~85℃ Store:-40℃~70℃ |
Working:-20℃~85℃ Store:-40℃~70℃ |
Working:-20℃~85℃ Store:-40℃~70℃ |
Humidity |
Relative humidity ≤93%, no condensation |
Relative humidity ≤93%, no condensation |
Relative humidity ≤93%, no condensation |
|
Altitude |
≤2000m |
≤2000m |
≤2000m |