Data Center Busway Monitoring Module,AMB100-A/AMB110-A Series

Data Center Busway Monitoring Module,AMB100-A/AMB110-A Series

Measured parameters:Voltage, current, frequency, active power, inactive power, power factor, active energy, inactive energy,2nd-63rd
harmonic, temperature, leakage
Rated value:3×220/380VAC
CT:AMB100-A:5A/2.5mA, 100A/20mA, 400A/100mA, 600A/100mA
AMB110-A:100A/20mA

 


Product Detail

PARAMETER

Download

Overview

AMB intelligent bus AC monitoring device is a new development to cater for smart power bus bar. It consists of a feeding detection module and a tapping detection module and integrates functions of conventional power measurements, electricity monitoring, consumption assessment and control. It also boasts the online alarm function and enables the independent off-line operation. It monitors the bus bar interface temperature in real time

Dimension

355bc39290a504f1f62a4a704dffe63
b129994d27716179591b19b58f535fc

Schematic Diagram

3f6dc62feaaa08d1b51e8d97659e7d5
9162bca087f8af4a16740476cb68759

Application

1ca395e9e85a6aee1ee4f98690d56de

Measured parameters Voltage, current, frequency, active power, inactive power, power factor, active energy, inactive energy, 2nd-63rd harmonic, temperature, leakage
Voltage Rated value 3×220/380VAC
Range ±20%
Overloading 1.2 times than the rated voltage value continuously or 2 times than the rated voltage value instantaneously per second
Current CT AMB100-A:5A/2.5mA, 100A/20mA, 400A/100mA, 600A/100mAAMB110-A:100A/20mA
Range 1%-120%
Overloading 1.2 times than the rated current value continuously or 10 times than the rated current value instantaneously per second
Input frequency 45-65Hz
Measurement accuracy Voltage/current:grade 0.2; active power/energy:grade 0.5; inactive power/energy:grade 1; temperature:±1℃
Auxiliary power supply AMB100/110-A(/W):triggered upon receipt of request signalAMB100/110-A(/W)-P1:follow the bus bar voltage
functions Temperature detection -20-150℃
Leakage 0-1A
Digital input 2 dry-contact inputs
Digital output 2 relay outputs; contact capacity:3A/30VDC, 3A/250VAC
Communication Via RS485/Modbus-RTU or LORA antenna
Installation Use DIN35mm rail
Protection IP20
Pollution level 2
Environment Temperature/ humidity/ altitude Working temperature:-20-60℃Storage temperature:-25-70℃Relative humidity:≤93%

Altitude:≤2500m

Safety Insulation The minimum insulation resistance between all terminals and conductive components of the shell is 100MΩ.
Withstanding voltage When a voltage of 2kV AC is applied between the voltage/ current input, relay output, RS485 port, auxiliary power supply and digital inputs, the leakage shall be less than 2mA and no breakdown or flashover shall occur in 1min..
Electromagnetic immunity Electrostatic discharge immunity Class 4
Radio frequency electromagnetic immunity Class 3
Transient burst immunity Class 4
Surge immunity Class 4