• head_banner

Digital Earth Leakage Relay,ASJ10L-LD1A

Digital Earth Leakage Relay,ASJ10L-LD1A

● The measurement of A-type after-current;

● The streamer display of current percentage;

● The setting of rated residual action current;

● The setting of non-driving time of limitation;

● Two-pair relay output;

● Possessing the function of on-the-spot and long-distance testing and resetting.

● LCD display

● RS485 Modbus-RTU


Product Detail

Technical parameters

Download

Overview

ASJ Series of action relay of after-current, low-voltage circuit break or low-voltage contactor can be made up for combined after-current production device, which is mainly applied for the TT and TN system distributing circuit with the alternating current 50Hz, the rated voltage 400V or below. ASJ Series of action relay of after-current is applied in the earth fault protection for the electric circuit, so as to prevent the equipment damage and the fire accident of electric equipment caused by the ground fault current, moreover, it also can provide indirect contact protection against the electric shock risk.

Display
LCD display

Comunication
RS485 Modbus-RTU

Frequency 
50Hz±5Hz

Auxiliary power supply
AC110V, AC220V, DC85 ~270V
(permissible error ±10%)

1
2

Consumption
≤5W

Installation
DIN rail 35mm

Dimension(L*W*H)
85×54×64mm

Typical Connection

3
4

Installation

5

Application

6

Technical Parameter

Indicator

AC type

A type

Power supply

Voltage range

AC110V、AC220V

(±10%)

AC/DC85~265V

Power dissipation

≤5W

Input

Rated residual operating current In

0.03、0.1、0.3、0.5(A)

0.03、0.05、0.1、0.3、0.5、1、3、5、10、30(A)note 3

Limit non-driving time △t

0.1、0.5(s)

0、0.06、0.1、0.2、0.3、0.5、0.8、1、4、10(s)note 4

Rated residual non-operating current Ino

50%In

50%In

Performance characteristics

Sinusoidal AC

Sinusoidal AC and pulsating DC

Frequency

50Hz±5Hz

50Hz±5Hz

Operating range

-20% ~ -10%In

-20% ~ -10%In

Output

Output mode

One is normally open and another is for transformation

One is normally closed or open, and another is for transformation

Contact capacity

5A 250VAC

5A 30VDC

AL1:8A 250VAC; 5A 30VDC

AL2:6A 250VAC; 5A 30VDC

Reset mode

Local reset or remote reset 

Local reset, remote reset or automatic reset

Installation and use environment

Temperature

Run temperature:-20℃ ~ +55℃,Storage temperature:-30℃ ~ +70℃

Humidity

≤95%RH,no condensation, and no corrosive gas places

Elevation

≤2000m

Class of pollution

Grade three

Installation category

Type Ⅲ

Note 3: ASJ10L-LD1A rated residual operating current IΔn is 10mA~30A continuously adjustable;

Note 4: ASJ10L-LD1A limit non-driving time Δt is 0~10S continuously adjustable.

Write your message here and send it to us